Send Message
Home ProductsAir Cooled Modular Chiller

Heating / Cooling 66kW Air Cooled Modular Chiller Electric Air Source Heat Pump

Heating / Cooling 66kW Air Cooled Modular Chiller Electric Air Source Heat Pump

  • Heating / Cooling 66kW Air Cooled Modular Chiller Electric Air Source Heat Pump
  • Heating / Cooling 66kW Air Cooled Modular Chiller Electric Air Source Heat Pump
Heating / Cooling 66kW Air Cooled Modular Chiller Electric Air Source Heat Pump
Product Details:
Place of Origin: China
Brand Name: EuroKlimat
Certification: ISO9001, ISO14001, OHSAS18001, CRAA, CQC
Model Number: EKAC 230BRLH
Payment & Shipping Terms:
Minimum Order Quantity: 1
Price: negotiation
Packaging Details: Carton
Delivery Time: 20 working days after received your payment
Payment Terms: L/C, T/T
Supply Ability: 50 pcs per month
Contact Now
Detailed Product Description
Product Name: Low-temp High-efficiency Model Air-cooled Heat Hump Unit Limiting Temperature: -20 ℃ Cooling And 48℃ Heating
Heating Capacity Range: 70 KW~1120 KW Cooling Capacity Range: 66 KW~1056 KW
COP: 3.68 IPLV: 4.33
High Light:

air cooled heat pump

,

heat pump outside unit

 

Low-temp high-efficiency model Air-cooled Heat Hump Unit

 

 

Specifications:

 

Technical data sheet

 

 

Model

 

EKAC 230BRLH

EKAC 460BRLH

EKAC         690 BRLH

EKAC          920BRLH

EKAC   1150BRLH

EKAC   1380BRLH

Unit combination

Master unit

EKAC230 BRLHM

EKAC230 BRLHM

EKAC230  BRLHM

EKAC230  BRLHM

EKAC230  BRLHM

EKAC230  BRLHM

slave unit

--

EKAC230 BRLHS

2EKAC230 BRLHS

3EKAC230  BRLHS

4EKAC230 BRLHS

5EKAC230 BRLHS

Nominal cooling  capacity

kW

66

132

198

264

330

396

USRT

18.77

37.54

56.31

75.08

93.85

112.62

×104kcal/h

5.67

11.34

17.01

22.68

28.35

34.02

Nominal heating capacity

kW

70

140

210

280

350

420

USRT

19.91

39.82

59.73

79.64

99.55

119.46

×104kcal/h

6.02

12.04

18.06

24.08

30.1

36.12

Total power of nominal    cooling capacity

kW

18.1

36.2

54.3

72.4

90.5

108.6

Total power of nominal    heating capacity

kW

19.0

38

57

76

95

114

Power supply

 

380V/3N~/50Hz

Refrigerant

Type

 

R22

Control

 

Electronic expansion valve

Compressor

Type

 

Fully hermetic volute compressor

Lubricant

 

Mineral oil (SUNISO 3GS)

Qty.

Set

2

4

6

8

10

12

Fan

Type

 

High-efficiency vacuum braze-welded panel type

Qty.

Set

2

4

6

8

10

12

Water side                 heat exchanger

Type

 

High-efficiency vacuum braze-welded panel type

Water flow for
cooling

3
m /h

11.4

22.8

34.2

45.6

57

68.4

Water flow rate in
heating mode

3
m /h

12.0

24

36

48

60

72

Water resistance

kPa

34

34

34

34

34

34

Recommended diameter for general inlet / outlet water pipe

inch

≥2

≥3

≥3

≥4

≥4

≥5

Power cable specification

Section area of live line

2
mm

≥10

≥35

≥70

≥95

≥120

≥150

Qty. of live lines

 

3

Section area of null line

2
mm

≥4

Qty. of null lines

 

1

Section area of grounding line

2
mm

≥10

≥16

≥35

≥50

≥60

≥75

Qty. of grounding lines

 

1

Dimensions

L x H

mm

2012×1840

Width

mm

880

2125

3370

4615

5860

7105

Unit weight

Net weight

kg

590

1180

1770

2360

2950

3540

Operating weight

kg

600

1200

1800

2400

3000

3600

 

Note:
■ Test conditions for nominal cooling capacity: outlet water temperature 7°C; water flow: 0.172m3/(h·kw); outdoor ambient temperature 35°C.
■ Test conditions for nominal heating capacity: outlet water temperature 45°C; water flow: 0.172m3/(h·kW); outdoor dry/web bulb temperature
7°C/6°C.
■ Water resistance at the air conditioner side includes water pressure drop of the unit and the attached Y-shaped filter.
■ Main Pipes of combined units need to be customized and installed on site. The diameter of the pipes must meet design requirements. EK
does not provide the pipes.
■ Modular units can be formed using the 1 - 16 basic modules of same type or of different types as per practical needs. The above table lists
the parameters for common module combinations.
■ For on-site electric wiring, see the name plate or installation menu of the unit.

 

Description

 

1. The low-temperature high-efficiency modular air cooled heat pump unit features a full-load COP up to 3.68, meeting the national standard for tier-1 energy saving products (3.4). Both the cooling and heating energy efficiency of the low-temperature high efficiency modular air-cooled heat pump unit is greatly improved to save operation cost for customers (value added). The energy efficiency is especially excellent with partial workload, bringing comfort to customers at much lower cost.

2. The EKAC low-temperature high-efficiency unit features leading-edge EVI (Enhanced Vapor Injection) compressors, increasing refrigerant recycling by as much as 20%. The evaporation capacity is improved by mid-pressure refrigerant intake. One compressor compresses refrigerant 2 times in each cycle. Half-M fins are used to improve the heat-exchange efficiency of the heat exchanger. The unit features state-of-the-art cross diagonal convection angles for stainless steel braze-welded panel-type heat exchanger and stainless steel braze welded panel-type economizer (used to increase the enthalpy differentiation between the inlet and outlet of the evaporator). An EXV is used to precisely control the operation of the unit.

3. The EKAC low-temperature high-efficiency modular air-cooled heat pump unit features excellent heating COP when the ambient temperature is low (20% higher than common air-cooled heat pump unit when the ambient temperature is -10°C). The lower ambient temperature limit is expanded from -10°C of common units to -20°C. This greatly improves cooling performance in areas where the winter is cold, reducing or eliminating the need for auxiliary heaters

4. Each modular unit has two power gears. When multiple modular units are combined, there could be many power gears. When working at a partial workload (99% of the operation time), the unit intelligently regulates the output based on the actual workload, making the operation efficiency even higher. With an optional 2-way valve water control feature, the unit can send out signals to cut off chilled water. This enables automatic flow control for pumps in line with the transducer, which helps save more energy.

5.  Currently, centralize heating by using heat pipes are very common. This type of heat provision wastes a lot of heat in the heating pipes, and is low in efficiency. Other defects include fixed heating period, environment pollution, difficult to maintain and collection fees, and not meeting national requirements on energy saving. The EKAC low-temperature high-efficiency modular air-cooled heat pump unit can provide enough heat in an ambient temperature as low as -20°C. The heating period, output capacity, and indoor temperature can be flexibly conditioned as required by the customer. The unit provides both heating and cooling functions, saving installation and maintenance costs. Unit of this series meets the trend for energy saving technologies, and is revolutionary compared with traditional heat provision solutions.

Heating / Cooling 66kW Air Cooled Modular Chiller Electric Air Source Heat Pump 0

Contact Details
Guangdong EuroKlimat Air-Conditioning & Refrigeration Co., Ltd

Contact Person: Mr. LENG Zhengliang

Tel: +86 13828797702

Fax: 86-0769-83622528

Send your inquiry directly to us (0 / 3000)